TST E-Learning Recap Areawww.tstengineering.co.uk
TST Engineering Services logo

Module 22 • Marine Engineering Oral Preparation

Power Generation, 3-Phase AC & Power Factor

A high-detail TST crib sheet for marine alternators, generator control, excitation, AVR response, synchronising, power factor, kW/kVAr/kVA sharing, PMS logic and switchboard protection.

3-Phase ACAVR & GovernorPower FactorSynchronising

Golden rule

Governor = Hz/kW.
AVR = volts/kVAr. Keep this separation clear in every oral answer.

Power triangle

kVA² = kW² + kVAr².
Power factor is kW divided by kVA.

Synchronising

V • f • sequence • angle.
Never close if phase sequence or angle is wrong.

How to use this Module 22 crib sheet

Use this infographic to convert electrical theory into MCA oral answers. Start with the principle, link it to the shipboard system, then state the fault consequence and safe operating action.

  • Explain three-phase AC generation and frequency calculation.
  • Separate governor, AVR, excitation and PMS functions.
  • Apply synchronising rules and recognise lamp/synchroscope indications.
  • Interpret power factor, active/reactive/apparent power and load sharing.
  • State practical protection responses for reverse power, earth fault, CTs and switchboard fires.
Start recap

01 • 3-Phase Generation

How a Marine Alternator Produces Three-Phase AC

Rotating magnetic field

DC excitation makes the rotor an electromagnet. As it rotates inside the stator, it cuts the stator conductors and induces AC voltage.

Three phases

Three stator winding groups are physically spaced 120 electrical degrees apart, giving R-Y-B phase voltages separated by 120°.

Generator rule

Fleming’s right-hand rule: thumb = motion, first finger = magnetic field, middle finger = induced current.

ROTOR 120°-spaced stator windings R Y B 120° 120° 120° Three-phase sine waves displaced by 120 electrical degrees +V 0 −V Electrical angle → R phase Y phase B phase

02 • Governor vs AVR

Do Not Mix Up Frequency and Voltage

ControllerActs onControlsParallel operation
GovernorPrime mover fuel / speedFrequency and active power kWkW load sharing and droop
AVRDC excitation to rotor fieldTerminal voltage and reactive power kVArkVAr sharing and voltage matching
PMSGenerator start/stop/load decisionsReserve power and automatic sequencingAuto synchronising, load shedding and unload/stop

Oral answer opener

“The governor is mechanical speed and kW; the AVR is magnetic field strength, voltage and kVAr. If I mix those up, the rest of the generator answer becomes wrong.”

03 • Frequency Formula

Poles, Speed and Output Frequency

f = P × N / 120

f = frequency in Hz, P = number of poles, N = rotor speed in rpm. Example: 4-pole alternator at 1800 rpm gives 60 Hz.

2-pole3000 rpm at 50 Hz
4-pole1500 rpm at 50 Hz
4-pole1800 rpm at 60 Hz
HzGovernor controlled

Transient frequency

When a heavy load starts, engine speed dips before the governor adds fuel. A strong oral answer links frequency recovery to governor response, fuel rack movement and prime-mover load acceptance.

04 • Excitation and AVR

Voltage Is Controlled by Rotor Field Strength

Excitation

Controlled DC supplied to the rotor field. More field current strengthens magnetic flux and raises induced stator EMF.

AVR loop

Sensing transformer measures terminal voltage; comparator compares it to reference; AVR adjusts firing/exciter output to correct the error.

PMG advantage

A PMG gives the AVR an independent power source, so voltage can recover during heavy motor starts or large transient dips.

SenseTerminal voltage feedback.
CompareMeasured voltage against setpoint.
AmplifyError signal drives excitation.
ExciteRotor field current changes.
CorrectTerminal voltage recovers.

05 • Synchronising

Four Conditions Before Closing the Breaker

Voltage

Incoming generator voltage must match busbar voltage; trim with AVR.

Frequency

Incoming set should be very slightly fast; trim with governor.

Phase sequence

R-Y-B must match the busbar. Rotating lamp pattern means do not close.

Phase angle

Close just before 12 o’clock with synchroscope moving slowly fast.

Out-of-phase closure: causes massive circulating current, torque shock, shaft stress, insulation damage and possible blackout. Never close on a stationary pointer unless it is proven at 12 o’clock and the synchronising equipment is healthy.

06 • Power Factor

kW, kVAr and kVA in the Power Triangle

Power triangle showing the relationship between kW, kVAr and kVA φ kW = active / true power kVAr = reactive kVA = apparent power PF = cos φ = kW / kVA 0 Useful work → Magnetising requirement ↑

PF = kW / kVA

Active power does useful work. Reactive power creates magnetic fields. Apparent power is the total current burden that heats the alternator windings.

kWGovernor / fuel
kVArAVR / excitation
kVATotal current
PFcos φ

07 • Load Sharing

Parallel Generators: What You Adjust and Why

kW sharing

Increase fuel/governor setting on one machine and reduce the other. Active load follows mechanical torque and prime-mover fuel input.

kVAr sharing

Adjust AVR voltage trim/excitation. Over-excited machines carry more lagging kVAr; under-excited machines can move toward leading PF.

Leading PF danger

Heavy under-excitation weakens rotor flux. The generator can lose synchronism, slip a pole and trip or damage equipment.

Memory line

“Fuel shares kW. Field shares kVAr. Current heats the alternator, so the machine is rated in kVA.”

08 • PMS and Blackout Recovery

Reserve Power, Auto Start and Load Shedding

Rising load

PMS monitors reserve power. If reserve falls below limit, it starts, synchronises and closes a standby generator before allowing heavy consumers.

Unload and stop

PMS gradually shifts kW off a surplus set, opens the breaker near zero load, runs the engine on idle to cool, then stops it.

Preferential trips

Non-essential consumers are shed in priority order to prevent overload and preserve essential services such as steering and propulsion support.

BlackoutLoss of main bus.
EDGEmergency generator restores critical power.
CauseIdentify and isolate the fault.
RestoreStart main generator and close safely.
ReloadBring consumers back in priority order.

09 • Protection and Practical Faults

What Trips, What It Protects and What You Do

Protection / faultWhat it detectsWhy it mattersOral action
Reverse powerkW flowing from busbar into generator.Alternator motors the failed diesel engine.Trip breaker, investigate fuel/governor/prime mover.
Earth fault on IT systemFirst insulation fault to hull.First fault alarms; second fault can short-circuit.Trace and clear without unnecessary blackout.
CT secondary openLive current transformer with open secondary.Can generate lethal high voltage.Short CT links before opening circuit.
Differential protectionCurrent entering and leaving stator differs.Internal alternator fault.Trip immediately and do not reclose until tested.
Short circuit vs overloadInstant massive fault vs delayed high load.Different trip time and protection purpose.Identify whether fault or load management issue.
Switchboard fireLive electrical fire.Electrocution/arcing/re-ignition risk.Isolate power before firefighting medium.

10 • Oral Exam Matrix

Say This First, Then Expand

  • Governor / AVR: “Governor controls engine speed, frequency and kW; AVR controls excitation, voltage and kVAr.”
  • Frequency: “Frequency depends on poles and rpm: f = P × N / 120.”
  • Excitation: “DC field current to the rotor creates the magnetic field; AVR varies this to control terminal voltage.”
  • Synchronising: “Match voltage, frequency, phase sequence and phase angle; close just before 12 with the incoming set slightly fast.”
  • Power factor: “PF is kW/kVA. Low PF means more current for the same useful kW, increasing alternator heating.”
  • Load sharing: “Use governor for kW; use AVR/excitation for kVAr.”
  • Leading PF: “Usually under-excitation; risk of losing synchronism or slipping a pole.”
  • Blackout: “Emergency generator first, identify cause, restore one main set, reload essential services progressively.”
Memory line 1Governor = Hz and kW.
Memory line 2AVR = volts and kVAr.
Memory line 3kVA heats the alternator.
Memory line 4Never close out of phase.
Memory line 5CT secondary must not be opened live.
Memory line 6Earth fault one alarms; fault two trips.